DST-13300 digital display three-phase AC power totaler controller
Classification:
Digital Display Electricity Accumulation Series
The DST-13300 series digital display three-phase AC power accumulator controller can be externally connected with standard signals of voltage and current transformers or directly connected with AC signals of current 5A and voltage 500V, and can be used for fixed-point processing by special DSP chip, high-speed and high-precision AD acquisition, and various connection modes can be selected, three-phase AC current, three-phase AC voltage, three-phase active power, three-phase reactive power, three-phase apparent power, three-phase power factor, power frequency cycle, harmonics, three-phase active energy, three-phase reactive energy and three-phase total energy can be measured simultaneously, and each function is clearly subdivided on the model. The output function can be analog output, communication output and cumulative pulse output. It is equipped with RS232/485 communication interface, supports standard MODBUS RTU communication protocol, and can be networked to realize centralized data management. It can be equipped with undervoltage and overload event alarm and fault event recording functions.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
General technical parameters
Voltage input
Input range: 0.0~500.0V AC/input impedance: 2MΩ
Current input
Input range: 0.01 ~ 5A AC/input impedance:<0.1Ω
Output signal
Analog output: 4 ~ 20mA (load resistance ≤ 480 Ω), 0 ~ 20mA (load resistance ≤ 480 Ω)
0 ~ 10mA (load resistance ≤ 960 Ω), 1~5V (load resistance ≥ 250KΩ)
0~5V (load resistance ≥ 250KΩ)Alarm output: relay control output-AC220V/2A, DC24V/2A (resistive load) Communication output: RS485/RS232 communication interface, baud rate 1200 ~ 9600bps can be set,
Using standard MODBUS RTU communication protocol, the RS-485 communication distance can reach 1km; the RS-232 communication distance can reach 150 meters.Cumulative pulse output: the cumulative pulse output of active energy, reactive energy and total energy can be selected, and the output is OC gate Terminal
Rated current: 18A Rated voltage: 400V
Use environment
Ambient temperature: -10~60 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas.
Working power supply
AC 100~240V (switching power supply),50-60HZ; DC 20~29V (switching power supply).
Power consumption
≤ 5W
Structure
Standard snap-in
-

Selection Guide
① Specifications and dimensions
② Input type ③ transmission output ④ Alarm output Code
Width * Height * Depth Code
Input Type Code
Output Type Code
Alarm limit A
C160*80*110mm horizontal
96*96*110mm wayI
V
W
Ep
E3p
War
Eq
VA
Es
COS
Hz
Harthree-phase alternating current
three-phase alternating voltage
Three-phase active power
Three-phase active energy
Three-phase active balance power
three-phase reactive power
three-phase reactive energy
three-phase apparent power
three-phase apparent electrical energy
three-phase power factor
Three-phase power frequency cycle
three-phase harmonicDefault
0
1
2
3
4No output
4~20mA
1~5V
0~10mA
0~5V
0~20mADefault
RL1
RL2No output
1 Limit alarm
2 Limit alarm⑤ Communication output ⑥ Pulse output ⑦ Power supply Code
Communication Type Code Output Type Code Voltage range Default
D1
D2No output
RS485
RS232Default
P0
No output
cumulative pulse outputA
D220V AC
24V DC⑨ Remarks No remarks can be omitted
苏公网安备32010402001819