DST-15610 series of digital heat accumulator control instrument for the field temperature, pressure, flow and other signals for collection, display, control, remote transmission, communication, printing and other processing, constitute a digital acquisition system and control system. The flow totalization controller is suitable for the flow totalization measurement and control of liquid, general gas, superheated steam, saturated steam, etc. The heat totalization controller is suitable for heating systems and heat exchange systems such as plumbing and heating, and realizes on-line measurement of heat and mass transfer, thus providing a basis for enterprise energy management, energy consumption measurement and technical economy.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
General technical parameters
Input
Input signal
Current
Voltage
Resistance
galvanic couple
input impedance
≤ 250Ω
≥500kΩ
Input current maximum limit
≤30mA
Input voltage
Maximum limit≤ 6V
Output
Current
Voltage
Relay
24V power distribution or feed
Output load capacity
≤ 500Ω
≥ 250 KΩ
(Note: The module must be replaced when higher load capacity is required)AC220V/0.5A (small)
DC24V/0.5A (small)
AC220V/2A (large)
DC24V/2A (large)≤30mA
Setting method
Panel touch key number setting; parameter setting value password lock; setting value power-off and permanent storage.
Use environment
Ambient temperature: 0~50 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas
Working power supply
AC 100~240V (switching power supply),(50-60HZ);
DC 20~29V (switching power supply)Power consumption
≤ 5W
Structure
Standard snap-in
Communication
Using standard MODBUS communication protocol, the RS-485 communication distance can reach 1km, and the RS-232 communication distance can reach 15 meters. Note: When the instrument is equipped with communication function, the communication converter is preferably an active converter
Note: 1.DST-15620 series power consumption ≤ 5W
-

Selection Guide
① Specifications and dimensions
② Input indexing number of the first flow signal/③ Input indexing number of the second pressure compensation or outlet temperature/④ Input indexing number of the third temperature compensation or inlet temperature Code
Width * Height * Depth Code
scale number (measuring range) Code
scale number (measuring range) Code
scale number (measuring range) A
B
C
D160*80*110mm (horizontal)
80*160*110mm (vertical)
96*96*110mm (mode)
96*48*110mm (horizontal)00
01
02
03
04
05
06
07
08
09
10
11
12Thermocouple B(400~1800 ℃)
Thermocouple S(0~1600 ℃)
Thermocouple K(0~1300 ℃)
Thermocouple E(0~1000 ℃)
Thermocouple T(-200.0~400.0 ℃)
Thermocouple J(0~1200 ℃)
Thermocouple R(0~1600 ℃)
Thermocouple N(0~1300 ℃)
F2(700~2000 ℃)
Thermocouple Wre3-25(0~2300 ℃)
Thermocouple Wre5-26(0~2300 ℃)
Thermal resistance Cu50(-50.0~150.0 ℃)
Thermal resistance Cu53(-50.0~150.0 ℃)13
14
15
16
17
18
19
20
21
22
23
24
25Thermal resistance Cu100(-50.0~150.0 ℃)
Thermal resistance Pt100(-200.0~650.0 ℃)
Thermal resistance BA1(-200.0~600.0 ℃)
Thermal resistance BA2(-200.0~600.0 ℃)
Linear resistance 0~400 Ω(-1999~9999)
Remote transmission resistance 0-350Ω (-1999~9999)
Remote resistance 30-350Ω (-1999~9999)
0~20mV (-1999~9999)
0~40mV (-1999~9999)
0~100mV (-1999~9999)
-20~20mV (-1999~9999)
-100~100mV (-1999~9999)
0~20mA (-1999~9999)26
27
28
29
30
31
32
33
34
35
36
55
56
Default0~10mA (-1999~9999)
4~20mA (-1999~9999)
0~5V (-1999~9999)
1~5V (-1999~9999)
-5~5V (-1999~9999)
0~10V (-1999~9999)(non-switchable)
0 ~ 10mA (-1999~9999)
4 ~ 20mA (-1999~9999)
0~5V (-1999~9999)
1~5V (-1999~9999)
Pulse input (0~10KHz)
Full switch
Special specifications
No input⑤ transmission output 1(OUT1) ⑥ Transformed output 2(OUT2) ⑦ Alarm output (relay contact output) ⑧ Communication output/external event input Code
Output Type (Load Resistance RL) Code
Output Type (Load Resistance RL) Code
Alarm limit Code
Communication interface/digital input interface Default
0
1
2
3
4
5
8No output
4-20mA(RL≤ 500Ω)
1-5V (rl≥250kΩ)
0-10mA(RL≤ 1KΩ)
0-5V (rl≥250kΩ)
0-20mA(RL≤ 500Ω)
0-10V (rl≥4kΩ)
Special specificationsDefault
0
1
2
3
4
5
8No output
4-20mA(RL≤ 500Ω)
1-5V (rl≥250kΩ)
0-10mA(RL≤ 1KΩ)
0-5V (rl≥250kΩ)
0-20mA(RL≤ 500Ω)
0-10V (rl≥4kΩ)
Special specificationsDefault
RL1
RL2No output
1 Limit alarm
2 Limit alarm
Default
D1
D2
D3
YNo output
RS485 communication interface (Modbus RTU)
RS232 communication interface (Modbus RTU)
RS232C print interface
Start, Stop, Clear⑨ Feed output ⑩ Power supply 11 Remarks Code
Feed output (output voltage) Code
Voltage range No remarks can be omitted Default
1P
2PNo output
1 feeder output
2 feeder outputs
For example, 2P(12/24) means the first route.
12V, the second 24V feed outputA
DAC/DC 100~240V(50/60Hz)
DC 12~36V
苏公网安备32010402001819