DST-15620 digital display volume accumulator controller

Classification:

Digital Cumulative Series

The DST-15620 digital display volume totalization controller can collect, display and convert the liquid level of various regular and irregular tanks in the industrial field into the corresponding tank volume, which is suitable for monitoring, controlling and collecting various process parameters.

Keywords: Isolator

• With two analog transmission outputs • Support RS485, RS232 serial interface, using standard MODBUS RTU communication protocol • With DC24V feed output for field transmitter power distribution • Optical isolation technology is adopted between input, output, power supply and communication Parameter setting password lock, parameter setting power-off permanent storage, with parameter recovery system original setting function setting function
  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • General technical parameters

    Input

    Input signal

    Current

    Voltage

    Resistance

    galvanic couple

    input impedance

    ≤ 250Ω

    ≥500kΩ

     

     

    Input current maximum limit

    ≤30mA

     

     

     

    Input voltage
    Maximum limit

     

    ≤ 6V

     

     

    Output

    Current

    Voltage

    Relay

    24V power distribution or feed

    Output load capacity

    ≤ 500Ω

    ≥ 250 KΩ
    (Note: The module must be replaced when higher load capacity is required)

    AC220V/0.5A (small)
    DC24V/0.5A (small)
    AC220V/2A (large)
    DC24V/2A (large)

    ≤30mA

    Setting method

    Panel touch key number setting; parameter setting value password lock; setting value power-off and permanent storage.

    Use environment

    Ambient temperature: 0~50 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas

    Working power supply

    AC 100~240V (switching power supply),(50-60HZ);
    DC 20~29V (switching power supply)

    Power consumption

    ≤ 5W

    Structure

    Standard snap-in

    Communication

    Using standard MODBUS communication protocol, the RS-485 communication distance can reach 1km, and the RS-232 communication distance can reach 15 meters. Note: When the instrument is equipped with communication function, the communication converter is preferably an active converter

    Note: 1.DST-15620 series power consumption ≤ 5W

  • 1

    Selection Guide

    ① Specifications and dimensions

    ② Enter the indexing number ③ Transformer output 1(OUT1) ④ Transformer output 2(OUT2)

    Code

    Width * Height * Depth

    Code

    scale number (measuring range)

    Code

    scale number (measuring range)

    Code

    scale number (measuring range)
     A
     B
    C

     

    160*80*110mm (horizontal)
    80*160*110mm (vertical)
    96*96*110mm (mode)
    25
    26
    27
    28
    29
    30
    31
    32
    33
    34
    35
    56
    0~20mA (-1999~9999)
    0~10mA (-1999~9999)
    4~20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    -5~5V (-1999~9999)
    0~10V (-1999~9999)(non-switchable)
    0 ~ 10mA (-1999~9999)
    4 ~ 20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    Special specifications
    Default
    0
    1
    2
    3
    4
    5
    8
    No output
    4-20mA(RL≤ 500Ω)
    1-5V (rl≥250kΩ)
    0-10mA(RL≤ 1KΩ)
    0-5V (rl≥250kΩ)
    0-20mA(RL≤ 500Ω)
    0-10V (rl≥4kΩ)
    Special specifications
    Default
    0
    1
    2
    3
    4
    5
    8
    No output
    4-20mA(RL≤ 500Ω)
    1-5V (rl≥250kΩ)
    0-10mA(RL≤ 1KΩ)
    0-5V (rl≥250kΩ)
    0-20mA(RL≤ 500Ω)
    0-10V (rl≥4kΩ)
    Special specifications
    ⑤ Alarm output (relay contact output) ⑥ Communication output (Note 1) ⑦ Feed output ⑧ Power supply

    Code

    Alarm limit

    Code

    Communication interface (communication protocol)

    Code

    Feed output (output voltage)

    Code

    Voltage range

    Default
    RL1
    RL2
    RL3
    RL4

    No output
    1 Limit alarm
    2 Limit alarm
    3 Limit alarm
    4 Limit alarm
    Default
    D1
    D2
    No output
    RS485 communication interface (Modbus RTU)
    RS232 communication interface (Modbus RTU)
    Default
    1P
    2P

     

     

     

    No output
    1 feeder output
    2 feeder outputs
    For example, 2P(12/24) means the first route.
    12V, the second 24V feed output
     
    A

    D
    AC/DC 100~240V
    (50/60Hz)
    DC 20~29V
    ⑨ Remarks

    No remarks can be omitted