DST-11300 digital display single-channel PID adjustment controller (simple)
Classification:
Digital display simple type series
The DST-11300 series digital display single-channel PID adjustment controller adopts fuzzy PID calculation formula, and the instrument starts the self-tuning function. According to the characteristics of the controlled object, the optimal parameters can be automatically found to achieve good control effect without manual tuning parameters. The temperature control accuracy basically reaches 0.5 ℃, without overshoot or undershoot, and the cost performance is high. Both models adopt modular structure, simple structure and convenient operation. Can be used with various types of sensors, transmitters.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
General technical parameters
Input
Input signal
Current
Voltage
Resistance
galvanic couple
input impedance
≤ 250Ω
≥500kΩ
Input current maximum limit
≤30mA
Input voltage maximum limit
≤ 6V
Output
Current
Voltage
Relay
24V power distribution or feed
Output load capacity
≤ 500Ω
≥ 250 KΩ
(Note: The module must be replaced when higher load capacity is required)AC220V/0.5A (small)
DC24V/0.5A (small)
AC220V/2A (large)
DC24V/2A (large)≤30mA
Setting method
Panel touch key number setting; parameter setting value password lock; setting value power-off and permanent storage.
Use environment
Ambient temperature: 0~50 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas
Working power supply
AC 100~240V (switching power supply),(50-60HZ);
DC 20~29V (switching power supply)Power consumption
≤ 5W
Structure
Standard snap-in
Communication
Using standard MODBUS communication protocol, the RS-485 communication distance can reach 1km, and the RS-232 communication distance can reach 15 meters. Note: When the instrument is equipped with communication function, the communication converter is preferably an active converter
Note: The allowable load capacity of instrument relays with external dimensions D, E and H is AC220V/0.5A and DC24V/0.5A when outputting
-

Selection Guide
① Specifications and dimensions ② Enter the indexing number Code Width * Height * Depth Code scale number (measuring range) Code scale number (measuring range) Code scale number (measuring range) A
B
C
D
E
F
H160*80*110mm (horizontal)
80*160*110mm (vertical)
96*96*110mm (mode)
96*48*110mm (horizontal)
48*96*110mm (vertical)
72*72*110mm (mode)
48*48*110mm (mode)00
01
02
03
04
05
06
07
08
09
10
11
12Thermocouple B(400~1800 ℃)
Thermocouple S(0~1600 ℃)
Thermocouple K(0~1300 ℃)
Thermocouple E(0~1000 ℃)
Thermocouple T(-200.0~400.0 ℃)
Thermocouple J(0~1200 ℃)
Thermocouple R(0~1600 ℃)
Thermocouple N(0~1300 ℃)
F2(700~2000 ℃)
Thermocouple Wre3-25(0~2300 ℃)
Thermocouple Wre5-26(0~2300 ℃)
Thermal resistance Cu50(-50.0~150.0 ℃)
Thermal resistance Cu53(-50.0~150.0 ℃)13
14
15
16
17
18
19
20
21
22
23
24
25Thermal resistance Cu100(-50.0~150.0 ℃)
Thermal resistance Pt100(-200.0~650.0 ℃)
Thermal resistance BA1(-200.0~600.0 ℃)
Thermal resistance BA2(-200.0~600.0 ℃)
Linear resistance 0~500 Ω(-1999~9999)
Remote transmission resistance 0-350Ω (-1999~9999)
Remote resistance 30-350Ω (-1999~9999)
0~20mV (-1999~9999)
0~40mV (-1999~9999)
0~100mV (-1999~9999)
Internal retention
Internal retention
0~20mA (-1999~9999)26
27
28
29
30
31
32
33
34
35
550~10mA (-1999~9999)
4~20mA (-1999~9999)
0~5V (-1999~9999)
1~5V (-1999~9999)
Internal retention
0~10V (-1999~9999)
0 ~ 10mA (-1999~9999)
4 ~ 20mA (-1999~9999)
0~5V (-1999~9999)
1~5V (-1999~9999)
Full switch③ Transformer output (OUT) Code Output Type (Load Resistance RL) 0
1
2
3
4
5
K1
K3
K4
D14-20mA(RL≤ 500Ω)
1-5V (rl≥250kΩ)
0-10mA(RL≤ 1KΩ)
0-5V (rl≥250kΩ)
0-20mA(RL≤ 500Ω)
0-10V (rl≥4kΩ)
Relay contact output
Single-phase SCR zero-crossing trigger pulse output
Solid state relay drive voltage output
RS485 communication interface (Modbus RTU)④ Alarm output (relay contact output) ⑤ Distribution output ⑥ Power supply Code Alarm limit Code Distribution output (output voltage) Code Voltage range Default
RL1
RL2No output
1 Limit alarm
2 Limit alarmDefault
PNo output
1 power distribution output (load current ≤ 30mA)
For example, "P(24)" indicates distribution output 24VA
D
AC/DC 100~240V(50/60Hz)
DC 20~29V⑦ Remarks Default No Comments