DST-15100 single-channel digital display controller

Classification:

Digital Enhanced Series

DST-15100 digital display single-channel control instrument for on-site temperature, pressure, liquid level, speed and other signals for collection, display, control, remote transmission, communication, printing and other processing, constitute a digital acquisition system and control system, widely used in electric power, petrochemical, metallurgy, light industry, pharmaceutical, aviation and many other fields.

Keywords: Isolator

• 15100 and 15200 series are single input, dual-screen LED digital display, and with light column analog indication function (0~100%) • 15710/15720 for dual-screen LED digital display, PV display measured value, SV display the current channel number • The 15740 is four-screen LED digital display, which can detect four measurement signals at the same time, and the measurement signals of each input channel do not interfere with each other • With 36~38 kinds of signal input function, each channel can input different signal types at the same time; measurement accuracy of 0.2%FS • With DC24V feed output for field transmitter power distribution • Optical isolation technology is adopted between input, output, power supply and communication Parameter setting password lock, parameter setting power-off permanent preservation, with parameter recovery system original setting function
  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • General technical parameters

    Input

    Input signal

    Current

    Voltage

    Resistance

    galvanic couple

    input impedance

    ≤ 250Ω

    ≥500kΩ

     

     

    Input current maximum limit

    ≤30mA

     

     

     

    Input voltage
    Maximum limit

     

    ≤ 6V

     

     

    Output

    Current

    Voltage

    Relay

    24V power distribution or feed

    Output load capacity

    ≤ 500Ω

    ≥250kΩ
    (Note: The module must be replaced when higher load capacity is required)

    AC220V/0.5A (small)
    DC24V/0.5A (small)
    AC220V/2A (large)
    DC24V/2A (large)

    ≤30mA

    Setting method

    Panel touch key number setting; parameter setting value password lock; setting value power-off and permanent storage.

    Use environment

    Ambient temperature: 0~50 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas

    Working power supply

    AC 100~240V (switching power supply),(50-60HZ);
    DC 20~29V (switching power supply)

    Power consumption

    ≤ 5W

    Structure

    Standard snap-in

    Communication

    Using standard MODBUS communication protocol, the RS-485 communication distance can reach 1km, and the RS-232 communication distance can reach 15 meters. Note: When the instrument is equipped with communication function, the communication converter is preferably an active converter

    Remarks: 1. The allowable load capacity of instrument relays with external dimensions D, E and H is AC220V/0.5A and DC24V/0.5A when outputting
    2.15700,15740 series output load capacity is AC220V/2A/DC24V/2A
    3.15700,15740 series power consumption is ≤ 4W

  • 1

    Selection Guide

    ① Specifications and dimensions

    ② Enter the indexing number

    Code

    Width * Height * Depth

    Code

    scale number (measuring range)

    Code

    scale number (measuring range)

    Code

    scale number (measuring range)
    A
    B
    C
    D
    E
    F
    H
    K
    L
    M

     

    160*80*110mm (horizontal)
    80*160*110mm (vertical)
    96*96*110mm (mode)
    96*48*110mm (horizontal)
    48*96*110mm (vertical)
    72*72*110mm (mode)
    48*48*110mm (mode)
    160*80*110mm (horizontal/light column)
    80*160*110mm (vertical/light column)
    96*96*110mm (mode/light column)
    00
    01
    02
    03
    04
    05
    06
    07
    08
    09
    10
    11
    12
    Thermocouple B(400~1800 ℃)
    Thermocouple S(0~1600 ℃)
    Thermocouple K(0~1300 ℃)
    Thermocouple E(0~1000 ℃)
    Thermocouple T(-200.0~400.0 ℃)
    Thermocouple J(0~1200 ℃)
    Thermocouple R(0~1600 ℃)
    Thermocouple N(0~1300 ℃)
    F2(700~2000 ℃)
    Thermocouple Wre3-25(0~2300 ℃)
    Thermocouple Wre5-26(0~2300 ℃)
    Thermal resistance Cu50(-50.0~150.0 ℃)
    Thermal resistance Cu53(-50.0~150.0 ℃)
    13
    14
    15
    16
    17
    18
    19
    20
    21
    22
    23
    24
    25
    Thermal resistance Cu100(-50.0~150.0 ℃)
    Thermal resistance Pt100(-200.0~650.0 ℃)
    Thermal resistance BA1(-200.0~600.0 ℃)
    Thermal resistance BA2(-200.0~600.0 ℃)
    Linear resistance 0~400 Ω(-1999~9999)
    Remote transmission resistance 0-350Ω (-1999~9999)
    Remote resistance 30-350Ω (-1999~9999)
    0~20mV (-1999~9999)
    0~40mV (-1999~9999)
    0~100mV (-1999~9999)
    -20~20mV (-1999~9999)
    -100~100mV (-1999~9999)
    0~20mA (-1999~9999)
    26
    27
    28
    29
    30
    31
    32
    33
    34
    35
    38
    55
    56
    0~10mA (-1999~9999)
    4~20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    -5~5V (-1999~9999)
    0~10V (-1999~9999)(non-switchable)
    0 ~ 10mA (-1999~9999)
    4 ~ 20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    0~600V(-1999~9999)(non-switchable)
    Full switch
    Special specifications

    ③ Transformer output 1(OUT1)

    ④ Transformer output 2(OUT2)

    ⑤ Alarm output (relay contact output)

    ⑥ Communication output

    Code

    Output Type (Load Resistance RL)

    Code

    Output Type (Load Resistance RL)

    Code

    Alarm limit

    Code

    Communication interface (communication protocol)

    Default
    0
    1
    2
    3
    4
    5
    8

    No output
    4-20mA(RL≤ 500Ω)
    1-5V (rl≥250kΩ)
    0-10mA(RL≤ 1KΩ)
    0-5V (rl≥250kΩ)
    0-20mA(RL≤ 500Ω)
    0-10V (rl≥4kΩ)
    Special specifications
    Default
    0
    1
    2
    3
    4
    5
    8
    No output
    4-20mA(RL≤ 500Ω)
    1-5V (rl≥250kΩ)
    0-10mA(RL≤ 1KΩ)
    0-5V (rl≥250kΩ)
    0-20mA(RL≤ 500Ω)
    0-10V (rl≥4kΩ)
    Special specifications
    Default
    RL1
    RL2
    RL3
    RL4

     

     

     

    No output
    1 Limit alarm
    2 Limit alarm
    3 Limit alarm
    4 Limit alarm
    Default
    D1
    D2
    D3

     

    No output
    RS485 communication interface (Modbus RTU)
    RS232 communication interface (Modbus RTU)
    RS232C print interface

    ⑦ Feed output

    ⑧ Power supply

    ⑨ Remarks

    Code

    Feed output (output voltage)

    Code

    Voltage range

    No remarks can be omitted

    Default
    1P
    2P

    No output
    1 feeder output
    2 feeder outputs
    For example, 2P(12/24) means the first route.
    12V, the second 24V feed output

    A
    D

    AC/DC 100~240V(50/60Hz) 
    DC 20~29V