undefined
undefined
undefined
+
  • undefined
  • undefined
  • undefined

DST-IS15/1P N-385FM type surge protector

Classification:

Power surge protector

DST-IS15 surge protector is suitable for AC 50Hz/60Hz;220V/380V power supply system, which can be used as overhead line without attenuation Direct lightning protection, which belongs to direct lightning protection products. The product uses a customized high-energy varistor, which can be used for arc extinguishing, intermittent flow requirements. Don't high level power lightning protection place.

Keywords: Isolator

• Nondestructive screening technology for components • Temperature controlled tripping/fusing design • Ensure no-freewheeling technology • Large current discharge capability Residual low, can effectively protect the terminal equipment Module anti-dull bolt design to prevent reverse insertion • Module quick release button for easy replacement • Module window discoloration design, fault/failure indication • Remote communication contact design, alarm signal remote transmission • DIN35mm standard rail mounting
  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • DST-IS15 technical parameters

    Model

    DST-IS15

    NPE-IS15

    According to the standard

    GB 18802.1-2011(IEC 61643-1: 2005,MOD), Class II Test

    AC nominal voltage Uo

    220V/380V

    Maximum continuous operating voltage Uc

    275Vac

    320Vac

    385Vac

    255Vac

    Nominal discharge current In

    50kA (8/20μs)

    Maximum discharge current Imax

    15kA (10/350μs)

    Voltage protection level Up(at In)

    2.0kv

    2.2kv

    2.5kv

    1.5kv

    Response time

    ≤ 25ns

    ≤100ns

    Maximum backup protection fuse

    250A(gL/gG)

    Short-circuit withstand capability at maximum back-up fuse Ip

    10kArms

    Operating temperature range

    -40 ℃ ~ 80 ℃

    Enclosure protection class

    IP20

    Protection mode

    L/N-PE

    N-PE

    Work Instructions

    When the window shows red, it means that the product has failed and needs to be replaced!

    SPD combination mode

    1p,2p,3p,4p, 1P N, 3P N

    Remote communication contact type

    Floating switching contact

    Maximum value of remote communication contact

    250VAC/0.1A      125VDC/0.2A      75VDC/0.5A

  • Selection Guide

    General wiring diagram