DST-S40/2P-385FM type surge protector
Classification:
Power surge protector
DST-S40 surge protector is suitable for AC 50Hz/60Hz;220V/380V power supply system, which can be used as the second power distribution in the building Level lightning protection, such as the floor distribution cabinet of high-rise buildings, the unit distribution cabinet of civil buildings. The maximum discharge current is 40kA.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
DST-S40 technical parameters
Model
DST-S40
NPE-S40
According to the standard
GB 18802.1-2011(IEC 61643-1: 2005,MOD), Class II Test
AC nominal voltage Uo
220V/380V
Maximum continuous operating voltage Uc
275Vac
320Vac
385Vac
480Vac
255Vac
Nominal discharge current In
20kA (8/20μs)
Maximum discharge current Imax
40kA (8/20μs)
Voltage protection level Up(at In)
1.35kv
1.5kv
1.8kv
2.0kv
1.5kv
Response time
≤ 25ns
≤100ns
Maximum backup protection fuse
125A(gL/gG)
Short-circuit withstand capability at maximum back-up fuse Ip
10kArms
Operating temperature range
-40 ℃ ~ 80 ℃
Enclosure protection class
IP20
Protection mode
L/N-PE
N-PE
Work Instructions
When the window shows red, it means that the product has failed and needs to be replaced!
SPD combination mode
1p,2p,3p,4p, 1P N, 3P N
Remote communication contact type
Floating switching contact
Maximum value of remote communication contact
250VAC/0.1A 125VDC/0.2A 75VDC/0.5A
-
Selection Guide
General wiring diagram


苏公网安备32010402001819