DST-813 Thin Distribution Current Isolator
Classification:
Power distribution analog input
DST-813 thin distribution current isolator provides isolated power supply voltage for two-wire and three-wire transmitters, and converts the DC current signal generated by the transmitter into the required signal to other instruments through isolation transmission. It can be used with the unit combination instrument and DCS, PLC and other systems to give field instruments signal isolation, signal conversion, signal distribution, signal processing, etc., so as to improve the anti-interference ability of the industrial production process automatic control system and ensure the stability and reliability of the system. This product variety is divided into one in and one out, one in and two out, two in and two out, and the input and output magnetic isolation.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
Technical parameters
Input Input signal 4-20mA、0-20mA、0-5V、1-5V、0-10V Input impedance Current impedance ≤ 50Ω Maximum input current/voltage ≤30mA Distribution voltage/maximum current 19 ~ 25 V/≤ 30mA Output Output signal 4-20mA、0-20mA、0-5V、1-5V、0-10V Output load 4-20mA, 0-20mA load resistance RL≤ 400 Ω;
0-5V, 1-5V load resistance RL≥ 250KΩ,0-10V load resistance RL≥ 500KΩGeneral technical parameters
Power Power DC20-32V Power consumption Single output power consumption: ≤ 1.5W; Dual output power consumption: ≤ 2.6W Other parameters Insulation resistance
(between input/output/power)≥ 100MΩ (at 500VDC) Insulation strength
(between input/output/power)2000Vrms (1 min, no spark) Working temperature -10~50 ℃ (no condensation, no icing) Relative humidity 25%~85%RH save temperature -10~60 ℃ (no condensation, no icing) temperature drift 0.0075%FS/℃ Installation method 35mm DIN rail mounting Mounting dimensions 13*108*121.2mm (width * height * depth) Transmission accuracy (20 ℃) 0.1%FS (0.2%FS ± 1 word for 815 temperature transmission series) Response time ≤ 2ms Weight About 130 grams Electromagnetic compatibility Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1) Applicable field equipment Two-wire, three-wire transmitter, DC current source -
Structural outline drawing

General Structure Outline Drawing

-

For example:
Input signal:0-20mA, output signal: 0-5V, one in and one out. Type selection: DST-81311-IS-25-3-D;
Input signal:0-20mA, output signal: 0-5V, one in and two out. Type selection: DST-81312-IS-25-3/3-D;
Input signal:0-20mA, output signal: 0-5V, two in and two out. Selection: DST-81322-IS-25/25-3/3;
Remarks:Input signal types can only be converted to proportional output signal types. For example, when the input is 4-20mA, the output type can only be 4-20mA or 1-5V. The current output and voltage output cannot be switched. It needs to be completed by changing the hardware. Please indicate clearly when ordering.
苏公网安备32010402001819