DST-811 Thin Voltage/Current Isolators
Classification:
Analog Input
DST-811 thin voltage/current isolator will be DC voltage or current signal through isolation transmission, converted into the required signal to other instruments. It can be used with the unit combination instrument and DCS, PLC and other systems to give field instruments signal isolation, signal conversion, signal distribution, signal processing, etc., so as to improve the anti-interference ability of the industrial production process automatic control system and ensure the stability and reliability of the system. This product variety is divided into one in and one out, one in and two out, two in and two out, and the input and output magnetic isolation.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
Input Input signal 4-20mA、0-20mA、0-5V、1-5V、0-10V Input impedance Current impedance ≤ 50Ω, voltage impedance ≥ 250KΩ Maximum input current/voltage ≤ 30mA/≤ 10.5V Current Isolator Output Output signal 4-20mA、0-20mA、0-5V、1-5V、0-10V Output load 4-20mA, 0-20mA load resistance RL≤ 400 Ω;
0-5V, 1-5V load resistance RL≥ 250KΩ,0-10V load resistance RL≥ 500KΩ
Voltage Isolator Output Output signal 4-20mA、0-20mA、0-5V、1-5V、0-10V Output load 4-20mA, 0-20mA load resistance RL≤ 400 Ω;
0-5V, 1-5V, 0-10V load resistance RL≥ 20KΩPower Power DC20-32V Power consumption Single output power consumption: ≤ 1.5W; Dual output power consumption: ≤ 2.6W Other parameters Insulation resistance
(between input/output/power)≥ 100MΩ (at 500VDC) Insulation strength
(between input/output/power)2000Vrms (1 min, no spark) Working temperature -10~50 ℃ (no condensation, no icing) Relative humidity 25%~85%RH save temperature -10~60 ℃ (no condensation, no icing) temperature drift 0.0075%FS/℃ Installation method 35mm DIN rail mounting Mounting dimensions 13*108*121.2mm (width * height * depth) Transmission accuracy (20 ℃) 0.1%FS Response time ≤ 2ms Weight About 130 grams Electromagnetic compatibility Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1) Applicable field equipment Two-wire, three-wire transmitter, DC current source -


-

For example:
Input signal:PT100 thermal resistance, output signal: 4-20mA, one in and one out. Type selection: DST-81511-IS-14-0-D;
Input signal:PT100 thermal resistance, output signal: 4-20mA, one in and two out. Type selection: DST-81512-IS-14-0/0-D;
Input signal:PT100 thermal resistance, output signal: 4-20mA, one in and two out. Type selection: DST-81512-IS-14-0/0-D;
Remarks:The current output and voltage output are not switchable and need to be completed by changing the hardware. Please indicate clearly when ordering.