DST-606X-EX-38-a/b-V24 type frequency input detection terminal isolation barrier
Classification:
Frequency input
The isolation barrier at the DST-606X-EX-38-a/b-V24 frequency input detection end can provide 24V power supply to the hazardous area instrument, and the frequency signal generated by the hazardous area instrument is transmitted to the safety side output through the isolation barrier. The input has high anti-interference performance. The product requires independent power supply, input/output/power three isolation. This product can be used in frequency signal source and other equipment. According to GB/T 3836.1-2021 and GB/T 3836.4-2021, it has passed the inspection and obtained the ccc certificate. It is suitable for installation and use in safe areas and can be used together with intrapexy safety equipment in Zone 0, Zone 1 and Zone 2 of explosive gas hazardous places.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
Technical parameters
Hazardous side Input signal Frequency signal (sine wave, square wave, triangle wave) input impedance ≥ 2M Amplitude range 0.2~9V Response time ≤ 1S Measurement range 1~10000Hz Resolution 0.1Hz Safety side Output signal type Analog output Output load characteristics Current output: RL≤ 500 Ω, voltage output: RL≥ 250KΩ
Transmission delay ≤ 10μs, signal transmission rate ≤ 9.6kbpsGeneral technical parameters
Power Power DC24V ±10% Power consumption Power consumption: ≤ 2.5W Other parameters Insulation strength
(Between Inthenine Safety End/Non-Inthenine Safety End)1500Vrms (1 min, no spark) Working temperature
Relative humidity-10~50 ℃ (no condensation, no icing)
25%~85%RHsave temperature -10~60 ℃ (no condensation, no icing) Installation method 35mm DIN rail mounting Mounting dimensions 17.5*111.4*121.2mm (width * height * depth) Transmission accuracy (20 ℃) 0.2%FS ± 1 word Weight About 130 grams Electromagnetic compatibility Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1) Applicable field equipment Two-wire, three-wire transmitter, DC current source -
Structural outline drawing

General Structure Exterior

-

For example:
Input signal: 0-5KHz, power distribution 12VDC, output signal: 4-20mA, one in and one out. Type selection: DST-60611-EX-38-0-V12(0-5KHz);
Input signal: 0-5KHz, power distribution 12VDC, output signal: 4-20mA, one in and two out. Selection: DST-60612-EX-38-0/0-V12(0-5KHz);
Remarks:The frequency range can be indicated on the back of the model number.