DST-607-EX switch quantity input isolated safety barrier

Classification:

Switching quantity input

DST-607X-EX-a/b-c/d switching value input detection terminal isolation barrier can accept switch or proximity switch input from dangerous area, and output to relay or transistor output on safety side through safety barrier isolation. It has input state detection indication and can carry out forward and reverse control. The product needs independent power supply, and input/output/power supply three isolation. It can be used in NAMUR proximity switches, switches and other field equipment (including intrinsically safe switches such as pressure, temperature and liquid level) that meet the DIN19234. It has passed the inspection according to GB/T 3836.1-2021 and GB/T 3836.4-2021 standards and obtained ccc certificate. It is suitable for installation and use in safe areas and can be used together with intrinsically safe equipment in areas 0, 1 and 2 of explosive gas hazardous places.

Keywords: Isolator

• National Instrument Explosion-proof Safety Supervision and Inspection Station (CNEX) certification • Explosion-proof sign [Exia Ga] IIC According to GB3836.1, GB3836.4, GB3836.20 standard inspection, to obtain ccc certificate • Single channel, dual channel This series of varieties have one in and one out, one in and two out, two in and two out. • DC voltage, current, thermal resistance, thermocouple input • Analog output, loop-powered • The signal type and test range of some products can be programmed by the supporting PC software • Plug-in terminals for easy installation and maintenance • Standard 35mm DIN rail clip-on mount
  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • Technical parameters

     

    Hazardous side
    Input signal Contact switch, proximity switch (frequency ≤ 5KHZ)
    Distribution voltage ≈ 8V (open circuit)
    Short-circuit current ≈ 8mA
    Safety side
    Output signal Relay or transistor output
    Switching quantity output Relay output drive capability: DC30V/2A,AC125V/0.6A; relay response time ≤ 5ms;
    In case of collector output (see Application 1 for connection mode): high level VCC≤ 30V, low level ≤ 2.5V;
    Emitter output (see application 2 for connection mode): high level VCC-2.5V, low level ≤ 0.5V
    Field switch closed or input loop current> 2.1mA, output relay or transistor on, channel
    Green indicator light; field switch open or input loop current <1.2mA, output relay or transistor
    No conduction, the channel red indicator light is on

     

    General technical parameters 

     

    Power
    Power DC24V ±10%
    Power consumption Power consumption: ≤ 2.5W
    Other parameters
    Insulation strength
    (Between Inthenine Safety End/Non-Inthenine Safety End)
    1500Vrms (1 min, no spark)

    Working temperature
    Relative humidity

    -10~50 ℃ (no condensation, no icing)
    25%~85%RH
    save temperature -10~60 ℃ (no condensation, no icing)
    Installation method 35mm DIN rail mounting
    Mounting dimensions 17.5*111.4*121.2mm (width * height * depth)
    Transmission accuracy (20 ℃) 0.2%FS ± 1 word
    Weight About 130 grams
    Electromagnetic compatibility Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1)
    Applicable field equipment Two-wire, three-wire transmitter, DC current source
  • Structural outline drawing

    结构外形图

    General Structure Exterior

     

    通用结构外型图

  •  

    1

     

    For example:

    Input signal: contact switch, output signal: relay, one in and one out. Type selection: DST-60711-EX-36-K1;

    Input signal: contact switch, output signal: relay, two in and two out. Selection: DST-60722-EX-36/36-K1/K1;

    Remarks:607X series can only choose one in and one out or two in and two out.