undefined
undefined
+
  • undefined
  • undefined

DST-11401 series intelligent temperature and humidity monitor

Classification:

Electrical cabinet environment monitor

This product is mainly used for power equipment (such as outdoor terminal box, high and low voltage control cabinet, photovoltaic communication cabinet, handcart switch cabinet, ring network switch cabinet, underground substation, box-type substation, circuit breaker mechanism box, instrument box, etc.) and other occasions that require automatic moisture removal, condensation prevention and antifreeze. It can effectively prevent all kinds of accidents caused by humidity, condensation and high temperature (low), and ensure the efficient and safe operation of automatic operation. The product has the advantages of small size, long life, three anti-treatment (moisture, salt spray, mold), convenient installation, simple operation, etc. It is a humidity and temperature monitoring product all the way, which can monitor the temperature and humidity of the environment in real time, automatically control the corresponding load, ensure that the temperature and humidity indicators meet the working standards, and effectively prevent condensation. When the sensor fails, the product automatically cuts off the load power supply to ensure that other equipment is not affected. In addition, the product has a forced start load function.

  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • Technical parameters

    Data Name Technical parameters
    Working power supply AC220V(± 10%) frequency 50/60Hz
    Conditions of use Working environment temperature -25 ℃ ~ +70 ℃; relative humidity ≤ 95% RH
    Humidity control range 0 ~ 99% RH, full range adjustable
    Temperature control range -40~95 ℃, full range adjustable
    Display mode 3 digital tube cycle display the current ambient temperature and humidity value
    Accuracy Temperature ± 2 ℃, humidity ± 5% RH
    Control return Temperature 0~20 ℃ (adjustable); humidity 0 ~ 20% RH (adjustable)
    Resolution 1RH%, 1 ℃
    Sampling period 2 times/second
    Control output Active contact output (normally open),AC220V 5A
    Load capacity Double working voltage, rated power resistive load AC220V 5A
    Withstand voltage High voltage 1500V frequency 50Hz alternating current for 1 minute, no breakdown and arcing phenomenon (national standard 1000V)
    Power consumption ≤ 5W
    Volume 48 × 48 × 78mm3
    Hole size 45.5 × 45.5mm2
  • Outline Data Drawing

    1

  • Ordering Guide

     

    DST-11401-G: Base type installation: Fix the 8-core base on the 35 mm guide rail or directly on the mounting plate through the mounting screw hole.

    DST-11401: Embedded installation: 45 0.5 × 45 0.5mm2 holes are opened on the installation panel, and the monitor is fixed on the panel through the installation bracket.