undefined
+
  • undefined

DST-11100 digital display single channel controller (simple)

Classification:

Digital display simple type series

DST-11100 series digital display single-channel control instrument (simple type) with field temperature, pressure, liquid level, speed and other signals for acquisition, display, control, remote transmission and communication.

Keywords: Isolator

  • Technical parameters
  • Structural outline drawing
  • Ordering Guide
  • General technical parameters

    Input

    Input signal

    Current

    Voltage

    Resistance

    galvanic couple

    input impedance

    ≤ 250Ω

    ≥500kΩ

     

     

    Input current maximum limit

    ≤30mA

     

     

     

    Input voltage maximum limit

     

    ≤ 6V

     

     

    Output

    Current

    Voltage

    Relay

    24V power distribution or feed

    Output load capacity

    ≤ 500Ω

    ≥ 250 KΩ
    (Note: The module must be replaced when higher load capacity is required)

    AC220V/0.5A (small)
    DC24V/0.5A (small)
    AC220V/2A (large)
    DC24V/2A (large)

    ≤30mA

    Setting method

    Panel touch key number setting; parameter setting value password lock; setting value power-off and permanent storage.

    Use environment

    Ambient temperature: 0~50 ℃; relative humidity: ≤ 85% RH; avoid strong corrosive gas

    Working power supply

    AC 100~240V (switching power supply),(50-60HZ);
    DC 20~29V (switching power supply)

    Power consumption

    ≤ 5W

    Structure

    Standard snap-in

    Communication

    Using standard MODBUS communication protocol, the RS-485 communication distance can reach 1km, and the RS-232 communication distance can reach 15 meters. Note: When the instrument is equipped with communication function, the communication converter is preferably an active converter

    Note: The allowable load capacity of instrument relays with external dimensions D, E and H is AC220V/0.5A and DC24V/0.5A when outputting

  • 1

    Selection Guide

    ① Specifications and dimensions ② Enter the indexing number
    Code Width * Height * Depth Code scale number (measuring range) Code scale number (measuring range) Code scale number (measuring range)
    A
    B
    C
    D
    E
    F
    H
    160*80*110mm (horizontal)
    80*160*110mm (vertical)
    96*96*110mm (mode)
    96*48*110mm (horizontal)
    48*96*110mm (vertical)
    72*72*110mm (mode)
    48*48*110mm (mode)
    00
    01
    02
    03
    04
    05
    06
    07
    08
    09
    10
    11
    12
    Thermocouple B(400~1800 ℃)
    Thermocouple S(0~1600 ℃)
    Thermocouple K(0~1300 ℃)
    Thermocouple E(0~1000 ℃)
    Thermocouple T(-200.0~400.0 ℃)
    Thermocouple J(0~1200 ℃)
    Thermocouple R(0~1600 ℃)
    Thermocouple N(0~1300 ℃)
    F2(700~2000 ℃)
    Thermocouple Wre3-25(0~2300 ℃)
    Thermocouple Wre5-26(0~2300 ℃)
    Thermal resistance Cu50(-50.0~150.0 ℃)
    Thermal resistance Cu53(-50.0~150.0 ℃)
    13
    14
    15
    16
    17
    18
    19
    20
    21
    22
    23
    24
    25
    Thermal resistance Cu100(-50.0~150.0 ℃)
    Thermal resistance Pt100(-200.0~650.0 ℃)
    Thermal resistance BA1(-200.0~600.0 ℃)
    Thermal resistance BA2(-200.0~600.0 ℃)
    Linear resistance 0~500 Ω(-1999~9999)
    Remote transmission resistance 0-350Ω (-1999~9999)
    Remote resistance 30-350Ω (-1999~9999)
    0~20mV (-1999~9999)
    0~40mV (-1999~9999)
    0~100mV (-1999~9999)
    Internal retention
    Internal retention
    0~20mA (-1999~9999)
    26
    27
    28
    29
    30
    31
    32
    33
    34
    35
    55
    0~10mA (-1999~9999)
    4~20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    Internal retention
    0~10V (-1999~9999)
    0 ~ 10mA (-1999~9999)
    4 ~ 20mA (-1999~9999)
    0~5V (-1999~9999)
    1~5V (-1999~9999)
    Full switch
    ③ Transformer output (OUT)
    Code Output Type (Load Resistance RL)
    0
    1
    2
    3
    4
    5
    D1
    4-20mA(RL≤ 500Ω)
    1-5V (rl≥250kΩ)
    0-10mA(RL≤ 1KΩ)
    0-5V (rl≥250kΩ)
    0-20mA(RL≤ 500Ω)
    0-10V (rl≥4kΩ)
    RS485 communication interface (Modbus RTU)
    ④ Alarm output (relay contact output) ⑤ Distribution output ⑥ Power supply
    Code Alarm limit Code Distribution output (output voltage) Code Voltage range
    Default
    RL1
    RL2
    No output
    1 Limit alarm
    2 Limit alarm
    Default
    P
    No output
    1 power distribution output (load current ≤ 30mA)
    For example, "P(24)" indicates distribution output 24V

    A

    D

    AC/DC 100~240V(50/60Hz)
    DC 20~29V
    ⑦ Remarks
    Default No Comments

    Note: K1,K3,K4 functions are unique to the 11300 series.