DST-807 switch intelligent isolator
Classification:
Switching quantity input
The DST-807 switch quantity intelligent isolator converts the received switch quantity signal into an isolated switch quantity signal output to provide the required switch quantity control or alarm signal for the external system. It has an input state detection indication and can be used together with the unit combination instrument and DCS, PLC and other systems. This product requires independent power supply, input/output/power three isolation.
Keywords: Isolator
- Technical parameters
- Structural outline drawing
- Ordering Guide
-
Technical parameters
Input Input signal Contact switch, proximity switch (frequency ≤ 5KHZ) Distribution voltage ≈ 8V (open circuit Short-circuit current ≈ 8mA Output Output signal Relay or transistor output Switching quantity output Relay capacity: DC30V/2A,AC125V/0.6A; relay response time ≤ 5ms;
Collector output: high level VCC≤ 30V, low level ≤ 2.5V;
Emitter output: high level VCC-2.5V, low level ≤ 0.5V;Input and output characteristics The field switch is closed or the input loop current is> 2.1mA, the output relay or transistor is on, and the channel green indicator light is on
The field switch is open or the input loop current is <1.2mA, the output relay or transistor is not conducting, and the channel red indicator light is onGeneral technical parameters
Power Power AC100~265V(50-60Hz) ;DC20-32V Power consumption ≤3W Other parameters Insulation resistance
(between input/output/power)≥ 100MΩ (at 500VDC) Insulation strength
(between input/output/power)2500Vrms (1 min, no spark) Working temperature -10~50 ℃ (no condensation, no icing) Relative humidity 25%~85%RH save temperature -10~60 ℃ (no condensation, no icing) temperature drift 0.005%FS/℃ Installation method 35mm DIN rail mounting Mounting dimensions 17.5*111.4*121.2mm (width * height * depth) Transmission accuracy (20 ℃) 0.2%FS ± 1 words Response time ≤ 1s Weight About 140 grams Electromagnetic compatibility Comply with GB/T18268 industrial equipment application requirements (IEC 61326-1) Applicable field equipment Two-wire, three-wire transmitter, DC current source -
Structural outline drawing

General Structure Outline Drawing

-

For example:
Input signal: current type proximity switch, output signal: relay, one in and one out, 220VAC power supply. Selection is: DST-80711-IS-DI1-K1-A
Input signal: current type proximity switch, output signal: relay, one in and two out, 220VAC power supply. Selection is: DST-80712-IS-DI1-K1/K1-A
Input signal: current type proximity switch, output signal: relay, two in and two out, 220VAC power supply. Selection: DST-80722-IS-DI1/DI1-K1/K1-A